When designing a grid-connected energy storage system (ESS), one of the most common and important questions is:
How many energy meters are required, and where should they be installed?
In most commercial, industrial, and residential applications, the answer is straightforward.
Standard Configuration: Two Bi-Directional Energy Meters
The most common and widely adopted configuration for grid-connected energy storage systems uses two bi-directional meters.
This setup is suitable for scenarios such as:
-
Self-consumption
-
Excess power export to the grid
-
Peak shaving and energy arbitrage
It provides accurate measurement for both grid settlement and energy management system (EMS) control.
Meter 1: Grid-Side Bi-Directional Meter
Installation Location
Installed at the Point of Common Coupling (PCC), typically inside the user’s main distribution board where the site connects to the public grid.
Function
This meter measures all energy exchanged between the user and the utility grid.
-
Forward energy: Electricity imported from the grid
-
Reverse energy: Electricity exported to the grid
Purpose
-
Used for utility billing and settlement
-
Enables calculation of:
-
Electricity purchase costs
-
Feed-in revenue or energy offset
-
-
Serves as the official reference for grid interaction compliance
This meter is essential for any system that allows grid import, export, or both.
Meter 2: Load-Side Bi-Directional Meter
Installation Location
Installed between the energy storage system (PCS/inverter) and the user’s loads.
Function
This meter measures the net local power balance of the site.
In practical terms, it reflects:
(PV generation + battery discharge) − load consumption
Interpretation of Meter Values
-
Positive value
-
Local generation exceeds load demand
-
Surplus energy can be exported to the grid or used to charge the battery
-
-
Negative value
-
Local generation is insufficient
-
Energy must be supplied by the grid or discharged from the battery
-
Purpose
This meter provides critical real-time data to the EMS, enabling intelligent control strategies such as:
-
Peak shaving
-
Load following
-
Battery charge/discharge scheduling
-
Maximizing self-consumption
-
Preventing unintended power export (zero-export control)
Why Two Meters Are Essential
Using both meters allows the energy storage system to:
-
Clearly distinguish grid interaction from local energy flow
-
Optimize charging and discharging strategies
-
Improve system efficiency and economic returns
-
Comply with grid regulations and operational constraints
This dual-meter configuration has become the industry standard due to its balance of simplicity, accuracy, and control capability.
Conclusion
For most grid-connected energy storage projects, two bi-directional energy meters form the foundation of a reliable and controllable system:
-
Grid-side meter — for grid exchange measurement and billing
-
Load-side meter — for EMS optimization and intelligent energy management
Proper meter selection, correct installation, and accurate data integration are key factors in ensuring the long-term performance and profitability of any energy storage system.
Post time: Jan-09-2026